Moeller NZML2-VE
|
||||||
|
Electronic Release 3-Pole Systems and cable protection, selectivity and generator protection Terminals Standard, terminal screws as accessories |
||||||
| North American | ||||||
|
Rated current = rated
uninterrupted current In = Iu |
Setting range
Overload releases |
Short-circuit releases | ||||
| Non Delayed | Delayed | |||||
| NZML2-VE100-NA | 100 | 50 - 100 | 1200 | 100 - 1000 | ||
| NZML2-VE160-NA | 160 | 80 - 160 | 1920 | 160 - 1600 | ||
| NZML2-VE250-NA | 250 | 125 - 250 | 3000 | 250 -2500 | ||
| European | ||||||
|
Rated current = rated
uninterrupted current In = Iu |
Setting range
Overload releases |
Short-circuit releases | ||||
| Non Delayed | Delayed | |||||
| NZML2-VE100 | 100 | 50 - 100 | 1200 | 100 - 1000 | ||
| NZML2-VE160 | 160 | 80 - 160 | 1920 | 160 - 1600 | ||
| NZML2-VE250 | 250 | 125 - 250 | 3000 | 250 -2500 | ||