Eaton offers a three- and four pole 30 mA ground fault (earth leakage) protection module for Series G E-, J- and L-Frame breakers. UL-listed modules are available for E, J and L molded case circuit breakers (MCCBs). The modules are bottom mounted for circuits up to 125A (E-Frame) 160 and 250 amperes (J-Frame), or 400 and 630 amperes for the L-Frame.
The module is completely selfc ontained because the current sensor, relay and power supply are located inside the product. Current pickup settings are selectable from 0.03–10 amperes for all IEC-rated modules and E and J UL-listed module, and 0.03– 30 amperes for the L ULlisted modules. Time delays are also selectable from Instantaneous–1.0 seconds for 0.10 ampere settings and above. A current pickup setting of 0.03 amperes defaults to an Instantaneous time setting regardless of the time dial’s position. Two alarm contacts come as standard: a 50% pretrip and a 100% after trip, both based only on earth leakagecurrent levels.
UL-Rated LG-Frame Earth Leakage Module Faceplate
IEC-Rated LG-Frame Earth Leakage Module Faceplate
Ampere
Rating |
Number of
Poles |
Part
Number |
125 | 3 | ELEBN3125G |
125 | 4 | ELEBN4125G |
Ampere
Rating |
Number of
Poles |
Part
Number |
125 | 3 | ELEBE3125G |
125 | 4 | ELEBE4125G |
Ampere
Rating |
Number of
Poles |
Part
Number |
150 | 3 | ELJBN3150W |
150 | 4 | ELJBN4150W |
250 | 3 | ELJBN3250W |
250 | 4 | ELJBN4250W |
Ampere
Rating |
Number of
Poles |
Part
Number |
160 | 3 | ELJBE3160W |
160 | 4 | ELJBE4160W |
250 | 3 | ELJBE3250W |
250 | 4 | ELJBE4250W |
Ampere
Rating |
Number of
Poles |
Part
Number |
400 | 3 | ELLBN3400W |
400 | 4 | ELLBN4400W |
600 | 3 | ELLBN3600W |
600 | 4 | ELLBN4600W |
Ampere
Rating |
Number of
Poles |
Part
Number |
400 | 3 | ELLBE3400W |
400 | 4 | ELLBE4400W |
630 | 3 | ELLBE3630W |
630 | 4 | ELLBE4630W |
NOTES:
(1) Shunt trip and undervoltage release cannot be used in an EG breaker connected to an earth leakage module.