Klockner Moeller
|
NZM10-400N |
TYPE ARTICLE NUMBER |
Switch
Block Ratings |
|
Switch Block Suitable For Insertion Of Trip Modules NZM10 switch blocks make up a complete breaker minus the protective trip module. See trip module data to complete the break assembly. |
400 |
n Supplied with toggle operator. n Supplied with bolt on connection as standard. |
NZM10-400N |
Type |
Long Time Response Current Setting |
Adjustable Instantaneous Pick-Up Setting |
Adjustable Short Tome Delay Pick Up Setting For Selectivity In Networks
Time Delay Range 0-1000 ms Delayed |
NZM10-400N/ZMVA-200-NA | 200 | 1000-9000 | 2 - 12 x Ir |
NZM10-400N/ZMVA-225-NA | 225 | ||
NZM10-400N/ZMVA-250-NA | 250 | ||
NZM10-400N/ZMVA-300-NA | 300 | ||
NZM10-400N/ZMVA-350-NA | 350 | ||
NZM10-400N/ZMVA-400-NA | 400 |
n Supplied with toggle operator. n Supplied with bolt on connection as standard. |
NZM10-400N |
Type |
Long Time Response Current Setting |
Adjustable Instantaneous Pick-Up Setting |
NZM10-400N/ZM-250-NA | 125 - 250 | 250 - 3000 |
NZM10-400N/ZM-400-NA | 200 - 400 | 400 - 4800 |
n Supplied with toggle operator. n Supplied with bolt on connection as standard. |
NZM10-400N |
Type |
Long Time Response Current Setting |
Adjustable Instantaneous
|
Adjustable Short Tome Delay Pick Up Setting For Selectivity In Networks
Time Delay Range 0-1000 ms Delayed |
200-400 | 1000-9000 | 400-4800 | |
n Supplied with toggle operator. n Supplied with bolt on connection as standard. |
NZM10-400N |
Type NZM10...(N)(S)/ZM(A)-...-NA molded case circuit
breakers are UL listed (UL 489) and CSA certified (22.2 No. 5.1) Inverse
time, Solid State Trip Circuit Breakers with a fixed or adjustable long
time response and adjustable instantaneous pick-up range. Type NZM10-...H/ZM(A)-...-NA molded case circuit breakers are UL listed (UL489) and CSA certified (22.2 No. 5.1) Current-limiting Inverse Time, Solid State Trip Circuit Breakers with a fixed or adjustable long time response and adjustable instantaneous pick-up range. |
||
Type |
Long Time |
Adjustable |
150 | 300 - 1800 | |
175 | 350 - 2100 | |
200 | 400 - 2400 | |
225 | 450 - 2700 | |
250 | 500 - 3000 | |
300 | 600 - 3600 | |
350 | 700 - 4200 | |
400 | 800 - 4800 | |
n Supplied with toggle operator. n Supplied with bolt on connection as standard. |
NZM10-400-N |
TYPE ARTICLE NUMBER |
AMPERE RATING |
NZM10-400 N/B-NA |
400 |
n Supplied with toggle operator. n Supplied with bolt on connection as standard. |
These switches
are virtually identical in construction to the NZM10 molded
case circuit breakers except that they are manual,
non-automatic switches without any overload or over current
protective features. They are equally rates up to 600A. All
molded-case switches are UL listed (UL 489) and CSA
certified (C22.2 Nr. 5.2), in conformity with IEC/EN 60
947-3 (switch disconnectors) and CE marked. Molded case Switches are tested to determine their acceptability for continuous operation at their marked rated load. In addition, they are tested at six times their full ampere rating to cover motor circuit applications and are suitable for use as motor circuit disconnects per NEC section 430-109 and CEC section 28-602. |
NZM10-400-N |
Type Article Number |
Circuit Breaker | Continuous Current Rating |
Adjustable Instantaneous Trip Response Range |
NZM10-400N/ZM-250-OBI-CNA | 600V AC, UL/SCA |
250 | 500 ... 3000 |
NZM10-400N/ZM-400-OBI-CNA | 400 | 800 ... 4800 |
n Supplied with toggle operator. n Supplied with bolt on connection as standard. |
Return to NZM10 |