UL Listed (UL 489) and CSA certified (22.2 No. 5.1) and have an additional short time delay pick up range for selectivity in energy distribution networks. The time delay response is adjustable form 0 to 1000 milliseconds.
|
CIRCUIT BREAKER | LONG TIME RESPONSE CURRENT SETTING | SETTING RANGES ADJUSTABLE INSTANEOUS PICK-UP SETTING |
ADJUSTABLE SHORT TOME DELAY PICK UP SETTING FOR SELECTIVITY IN NETWORKS
TIME DELAY RANGE 0-1000 ms DELAYED |
NORMAL INTERRUPTING CAPACITY
42 kA at 480 V 50/60 HZ 35 kA at 600 V 50/60 HZ |
HIGH INTERRUPTING CAPACITY 100 kA at 480 V 50/60 HZ 50 kA at 600 V 50/60 HZ |
WITH FIXED LONG TIME RESPONSE SETTING n Supplied with toggle operator. Refer to --- table for additional handle types. n Supplied with bolt on connection as standard. For line and load field wiring terminals for cable connection refer to --- table for details on available terminals. |
200 | 1000-9000 | 2 - 12 x Ir | ||
225 | 1000-9000 | 2 - 12 x Ir | |||
250 | 1000-9000 | 2 - 12 x Ir | |||
300 | 1000-9000 | 2 - 12 x Ir | |||
350 | 1000-9000 | 2 - 12 x Ir | |||
400 | 1000-9000 | 2 - 12 x Ir | |||
500 | 1000-9000 | 2 - 12 x Ir | |||
600 | 1000-9000 | 2 - 12 x Ir | |||
WITH ADJUSTABLE LONG TIME RESPONSE SETTINGS n Supplied with toggle operator. Refer to --- table for additional handle types. n Supplied with bolt on connection as standard. For line and load field wiring terminals for cable connection refer to --- table for details on available terminals. |
200-400 | 1000-9000 | 400-4800 | ||
300-600 | 1000-9000 | 600-7200 |
NZM10 Overview |
1. Overload Relay | 2. Amplifier modules or suppressor circuit |
3. Pneumatic timer modules | 4. Mechanical latching modules |
5. Additional 4th pole from DIL0M(-G) | 6. Top mounting auxiliary contact |
7. Side mounting auxiliary contact | Enclosure |
Return to NZM10 |
Return to NZM10 Accessories |
© 2016 KMParts.com, Inc. All rights reserved.