Eaton Moeller NZM1 Technical Information

NZMB1 NZMC1 NZMN1 NZMH1
Switching Capacity 63 121 187 220
240 V IcmkA 53 76 105 220
400/415 V 63 74 74
440 V -- 24 40 40
525 V -- 14 17 17
690 V
Rated short-circuit breaking capacityIcn
Icuto IEC/EN 60947 operating sequence O-t-CO
240 V 50/60 IcukA 30 55 85 100
400/415 V 50/60 Hz 25 36 50 100
440 V 50/60 25 30 35 35
525 V 50/60 12 20 20
690 V 50/60 8 10 10
500 V DC 15 30
750 V DC
Icsto IEC/EN 60947 operating sequence O-t-CO-t-CO
240 V 50/60 Hz IcskA 30 55 85 100
400/415 V 50/60 Hz 25 36 50 50
440 V 50/60 Hz 18.5 22.5 35 35
525 V 50/60 Hz 6 10 10
690 V 50/60 Hz 4 7.5 7.5
Utilization category to IEC/EN 60947-2 A A A A
Rated operational withstand current
t = 0.3 s IcwkA
t = 1 s
Rated making and breaking capacity
AC-1
400/415 V 50/60 Hz IeA 160 160 160 160
690 V 50/60 Hz 160 160 160 160
AC-3
400/415 V 50/60 Hz IeA 160 160 160 160
690 V 50/60 Hz 160 160 160 160
DC-1
500 V DC IeA 125 125
750 V DC
DC-3
500 V DC IeA 125 125
750 V DC
Life Mechanical Operations 2000 2000 2000 2000
Max.Operatingfrequency S/h 120 120 120 120
Life, electrical
AC-1
400/415 V 50/60 Hz Operations 10000 10000 10000 10000
690 V50/60 Hz 7500 7500 7500
AC-3
400/415 V 50/60 Hz Operations 7500 7500
690 V50/60 Hz 5000 5000
DC-1
500 V DC Operations 10000 10000
750 V DC
DC-3
500 V DC Operations 5000 5000
750 V DC