Eaton/Moeller
S811+V50N3S
S811 Plus Soft Starter with DIM |
|
Product Description
Eaton’s S811+ offers all the popular features of the S801+ and adds new enhanced functionality with the new Digital Interface Module (DIM), communications, metering, monitoring and diagnostics capabilities.
The S811+ is designed to be a complete package, combining the silicon controlled rectifiers (SCRs), bypass contactor and overload in one, very compact unit.
S811+V50N3S
Frame Size = V |
S811+V50N3S Standard Duty Ratings
|
Rated
Current |
Three-Phase Motors |
kW Rating (50 Hz) |
hp Rating (60 Hz) |
200V |
230V |
460V |
575–600V |
230V |
380–400V |
440V |
1.0SF |
1.15SF |
1.0SF |
1.15SF |
1.0SF |
1.15SF |
1.0SF |
1.15SF |
Standard Duty - 15 Second Ramp, 300%
Current Limit at 40°C, Inline Connection |
500 |
150 |
257 |
300 |
150 |
150 |
200 |
150 |
400 |
350 |
500 |
450 |
Severe Duty - 30 Second Ramp and/or 450% Current Limit at 50°C, Inline Connection |
365 |
110 |
185 |
220 |
125 |
100 |
150 |
125 |
300 |
250 |
350 |
300 |
Standard Duty - 15 Second Ramp, 300% Current Limit at 40°C, Inside-the-Delta Connection |
865 |
150 |
257 |
300 |
250 |
250 |
300 |
250 |
600 |
550 |
750 |
700 |
Severe Duty - —30 Second Ramp and/or 450% Current Limit at 50°C, Inside-the-Delta Connection |
623 |
110 |
185 |
220 |
200 |
150 |
250 |
200 |
450 |
400 |
550 |
450 |
S811+V50N3S Specifications
|
Description |
S811+V50… |
S811+V65… |
S811+V72… |
S811+V85… |
S811+V10… |
Max. current
capacity (A) |
500 |
650 |
720 |
850 |
1000 |
FLA range |
156–500 |
203–650 |
225–720 |
265–580 |
320–1000 |
General Information |
Bypass
mechanical
lifespan |
10M |
10M |
10M |
10M |
10M |
Insulating
voltage Ui |
660 V |
660 V |
660 V |
660 V |
660 V |
Ramp
time range |
0.5–180 seconds
(0.5–360 seconds S811+ Premium) |
0.5–180 seconds
(0.5–360 seconds S811+ Premium) |
0.5–180 seconds
(0.5–360 seconds S811+ Premium) |
0.5–180 seconds
(0.5–360 seconds S811+ Premium) |
0.5–180 seconds
(0.5–360 seconds S811+ Premium) |
Resistance
to vibration |
3g |
3g |
3g |
3g |
3g |
Resistance
to shock |
15g |
15g |
15g |
15g |
15g |
Electrical Information |
Operating
voltage |
200–600 V |
200–600 V |
200–600 V |
200–600 V |
200–600 V |
Operating frequency |
47–63 Hz |
47–63 Hz |
47–63 Hz |
47–63 Hz |
47–63 Hz |
Overload
setting |
30–100% |
30–100% |
30–100% |
30–100% |
30–100% |
Trip class |
5, 10, 20 and 30 |
5, 10, 20 and
30 |
5, 10, 20 and 30 |
5, 10, 20 and 30 |
5, 10, 20 and 30 |
Cabling Capacity (IEC 947) |
Number
of conductors |
2, 4 or 6 |
2, 4 or 6 |
2, 4 or 6 |
2, 4 or 6 |
2, 4 or 6 |
Wire sizes |
2/0 to 500 kcmil |
2/0 to 500 kcmil |
2/0 to 500 kcmil |
2/0 to 500 kcmil |
2/0 to 500 kcmil |
Type of
connectors |
Add-on lug kit |
Add-on lug kit |
Add-on lug kit |
Add-on lug kit |
Add-on lug kit |
Control Wiring
(12-Pin) |
Wire sizes
in AWG |
22 - 14 |
22 - 14 |
22 - 14 |
22 - 14 |
22 - 14 |
Number of
conductors (stranded) |
2 (or one AWG 12) |
2 (or one AWG
12) |
2 (or one AWG 12) |
2 (or one AWG 12) |
2 (or one AWG 12) |
Torque
requirements
in lb-in |
3.5 |
3.5 |
3.5 |
3.5 |
3.5 |
Solid, stranded
or flexible max.
size in mm2 |
3.31 |
3.31 |
3.31 |
3.31 |
3.31 |
Control Power Requirements |
Voltage range
(24V ±10%) |
21.6–26.4 |
21.6–26.4 |
21.6–26.4 |
21.6–26.4 |
21.6–26.4 |
Steady-state
current amps |
1.0 |
1.0 |
1.0 |
1.0 |
1.0 |
Inrush current amps |
10 |
10 |
10 |
10 |
10 |
Ripple |
1% |
1% |
1% |
1% |
1% |
Relays (1) Class A and C |
Voltage AC -
maximum |
240 |
240 |
240 |
240 |
240 |
Voltage DC -
maximum |
120 |
120 |
120 |
120 |
120 |
Amps -
maximum |
3 |
3 |
3 |
3 |
3 |
Environment |
Temperature -
operating |
–30° to 50° C
no derating)
consult
factory for
operation >50° C |
–30° to 50° C
no derating)
consult
factory for
operation >50° C |
–30° to 50° C
no derating)
consult
factory for
operation >50° C |
–30° to 50° C
no derating)
consult
factory for
operation >50° C |
–30° to 50° C
no derating)
consult
factory for
operation >50° C |
Temperature -
storage |
–50° to 70° C |
–50° to 70° C |
–50° to 70° C |
–50° to 70° C |
–50° to 70° C |
Altitude |
<2000m -
consult factory
for operation
>2000m |
<2000m -
consult factory
for operation
>2000m |
<2000m -
consult factory
for operation
>2000m |
<2000m -
consult factory
for operation
>2000m |
<2000m -
consult factory
for operation
>2000m |
Humidity |
<95%
noncondensing |
<95%
noncondensing |
<95%
noncondensing |
<95%
noncondensing |
<95%
noncondensing |
Operating position |
Any |
Any |
Any |
Any |
Any |
Pollution degree
IEC947-1 |
3 |
3 |
3 |
3 |
3 |
Impulse withstand
voltage
IEC947-4-1 |
6000 V |
6000 V |
6000 V |
6000 V |
6000 V |
Part Number Selection Guide
|
|