Description |
S811+N37… |
S811+N66… |
S811+R10+… |
S811+R13… |
Max. current
capacity (A) |
37 |
66 |
105 |
135 |
FLA range |
11–37 |
20–66 |
32–105 |
42–135 |
General Information |
Bypass
mechanical
lifespan |
10M |
10M |
10M |
10M |
Insulating
voltage Ui |
660 V |
660 V |
660 V |
660 V |
Ramp
time range |
0.5–180 seconds
(0.5–360 seconds
S811+ Premium) |
0.5–180 seconds
(0.5–360 seconds S811+ Premium) |
0.5–180 seconds
(0.5–360 seconds
S811+ Premium) |
0.5–180 seconds
(0.5–360 seconds
S811+ Premium) |
Resistance
to vibration |
3g |
3g |
3g |
3g |
Resistance
to shock |
15g |
15g |
15g |
15g |
Electrical Information |
Operating
voltage |
200–600 V |
200–600 V |
200–600 V |
200–600 V |
Operating frequency |
47–63 Hz |
47–63 Hz |
47–63 Hz |
47–63 Hz |
Overload
setting |
30–100% |
30–100% |
30–100% |
30–100% |
Trip class |
5, 10, 20 and 30 |
5, 10, 20 and
30 |
5, 10, 20 and 30 |
5, 10, 20 and 30 |
Cabling Capacity (IEC 947) |
Number
of conductors |
1 |
1 |
1 |
1 |
Wire sizes |
22–14 |
22–14 |
22–14 |
22–14 |
Type of
connectors |
Box lug |
Box lug |
Box lug |
Box lug |
Control Wiring
(12-Pin) |
Wire sizes
in AWG |
22 - 14 |
22 - 14 |
22 - 14 |
22 - 14 |
Number of
conductors (stranded) |
2 (or one AWG 12) |
2 (or one AWG
12) |
2 (or one AWG 12) |
2 (or one AWG 12) |
Torque
requirements
in lb-in |
3.5 |
3.5 |
3.5 |
3.5 |
Solid, stranded
or flexible max.
size in mm2 |
3.31 |
3.31 |
3.31 |
3.31 |
Control Power Requirements |
Voltage range
(24V ±10%) |
21.6–26.4 |
21.6–26.4 |
21.6–26.4 |
21.6–26.4 |
Steady-state
current amps |
1.0 |
1.0 |
1.0 |
1.0 |
Inrush current amps |
10 |
10 |
10 |
10 |
Ripple |
1% |
1% |
1% |
1% |
Relays (1) Class A and C |
Voltage AC -
maximum |
240 |
240 |
240 |
240 |
Voltage DC -
maximum |
120 |
120 |
120 |
120 |
Amps - maximum |
3 |
3 |
3 |
3 |
Environment |
Temperature -
operating |
–30° to 50° C
no derating)
consult
factory for
operation >50° C |
–30° to 50° C
no derating)
consult
factory for
operation >50° C |
–30° to 50° C
no derating)
consult
factory for
operation >50° C |
–30° to 50° C
no derating)
consult
factory for
operation >50° C |
Temperature -
storage |
–50° to 70° C |
–50° to 70° C |
–50° to 70° C |
–50° to 70° C |
Altitude |
<2000m -
consult factory
for operation
>2000m |
<2000m -
consult factory
for operation
>2000m |
<2000m -
consult factory
for operation
>2000m |
<2000m -
consult factory
for operation
>2000m |
Humidity |
<95%
noncondensing |
<95%
noncondensing |
<95%
noncondensing |
<95%
noncondensing |
Operating position |
Any |
Any |
Any |
Any |
Pollution degree
IEC947-1 |
3 |
3 |
3 |
3 |
Impulse withstand
voltage IEC947-4-1 |
6000 V |
6000 V |
6000 V |
6000 V |