hp & kW Ratings - 10 Second Ramp, One Start per Hour,
|
Motor Power (hp) |
Motor Power (kW) |
Maximum Allowable Breaker Size |
Maximum Allowable Fuse Size |
|||||
---|---|---|---|---|---|---|---|---|
Rated Current (A) |
200 V | 230 V | 480 V | Rated Current (A) |
230 V | 400 V | ||
3.7 | 0.75 | 0.75 | 2 | 3.8 | 0.75 | 1.5 | HFD3015 | 15A Class RK5 |
Motor Power (hp) |
Motor Power (kW) |
Maximum Allowable Breaker Size |
Maximum Allowable Fuse Size |
|||||
---|---|---|---|---|---|---|---|---|
Rated Current (A) |
200 V | 230 V | 480 V | Rated Current (A) |
230 V | 400 V | ||
3 | 0.5 | 0.5 | 1.5 | 0.33 | 1 | 1.5 | HFD3015 | 15A Class RK5 |
XTOB Overload (Direct Connect) (1) |
XTOE Overload (1) |
PKE MMP | MMP (1) | Connection Kit to MMP |
---|---|---|---|---|
XTOB004BC1 | XTOE005BCS | XTPE012BCS | XTPR004BC1 | XTPAXTPCB |
DS7-342SX004N0-N Specifications |
---|
Rated Control Circuit | Part Number | |||
---|---|---|---|---|
24 Vac/Vdc 110/230 Vac 24 Vdc |
DS7-340SX004N0-N DS7-342SX004N0-N DS7-34DSX004N0-D |
DS7-340SX007N0-N DS7-342SX007N0-N DS7-34DSX007N0-D |
DS7-340SX009N0-N DS7-342SX009N0-N DS7-34DSX009N0-D |
DS7-340SX012N0-N DS7-342SX012N0-N DS7-34DSX012N0-D |
General | ||||
Standards | IEC/EN 60947-4-2; GB14048.6; UL508; CSA-C22.2 No 0-M91; CSA-C22.2 No 14-05 CE marking |
IEC/EN 60947-4-2; GB14048.6; UL508; CSA-C22.2 No 0-M91; CSA-C22.2 No 14-05 CE marking |
IEC/EN 60947-4-2; GB14048.6; UL508; CSA-C22.2 No 0-M91; CSA-C22.2 No 14-05 CE marking |
IEC/EN 60947-4-2; GB14048.6; UL508; CSA-C22.2 No 0-M91; CSA-C22.2 No 14-05 CE marking |
Certifications marking |
UL/CE/CSA/C-Tick | UL/CE/CSA/C-Tick | UL/CE/CSA/C-Tick | UL/CE/CSA/C-Tick |
Ambient temperature (operation) °C |
0 to 40 °C, above 40 °C de-rate linearly by 1% of rated current per Celsius to 60 °C –40 to +40 °C for low temperature version |
0 to 40 °C, above 40 °C de-rate linearly by 1% of rated current per Celsius to 60 °C –40 to +40 °C for low temperature version |
0 to 40 °C, above 40 °C de-rate linearly by 1% of rated current per Celsius to 60 °C –40 to +40 °C for low temperature version |
0 to 40 °C, above 40 °C de-rate linearly by 1% of rated current per Celsius to 60 °C –40 to +40 °C for low temperature version |
Ambient temperature (storage) °C | –25 to 55 °C | –25 to 55 °C | –25 to 55 °C | –25 to 55 °C |
Altitude | 0–1000m, above 1000m de-rate linearly by 2.5% of rated current per 100m to a maximum of 2000m |
0–1000m, above 1000m de-rate linearly by 2.5% of rated current per 100m to a maximum of 2000m |
0–1000m, above 1000m de-rate linearly by 2.5% of rated current per 100m to a maximum of 2000m |
0–1000m, above 1000m de-rate linearly by 2.5% of rated current per 100m to a maximum of 2000m |
Installation | Vertical | Vertical | Vertical | Vertical |
Protection class | IP20 | IP20 | IP20 | IP20 |
Protection class applies to the front and operator control and display elements. Protection type from all sides is IP00. |
With optional covers from the NZM range, protection type IP40 from all sides can be achieved |
With optional covers from the NZM range, protection type IP40 from all sides can be achieved |
With optional covers from the NZM range, protection type IP40 from all sides can be achieved |
With optional covers from the NZM range, protection type IP40 from all sides can be achieved |
Busbar tag shroud | Back of hand and finger-proof (from front face) |
Back of hand and finger-proof (from front face) |
Back of hand and finger-proof (from front face) |
Back of hand and finger-proof (from front face) |
Overvoltage category/ pollution degree |
II/2 | II/2 | II/2 | II/2 |
Shock resistance | 8g/11ms | 8g/11ms | 8g/11ms | 8g/11ms |
Vibration resistance according to EN 60721-3-2 |
2M2 | 2M2 | 2M2 | 2M2 |
Mean heat dissipation at rated duty cycle (W) |
0.2 | 0.35 | 0.35 | 0.6 |
Radio interference | B | B | B | B |
Main Circuit | ||||
Rated operational voltage (V) |
230–460 Vac | 230–460 Vac | 230–460 Vac | 230–460 Vac |
Mains frequency (Hz) | 50/60 Hz | 50/60 Hz | 50/60 Hz | 50/60 Hz |
Rated operation current AC 53 (Ie) |
4 | 7 | 9 | 12 |
Motor Power Ratings | ||||
200 V (hp) | 0.75 | 1.5 | 2 | 3 |
230 V (hp) | 0.75 | 2 | 2 | 5 |
480 V (hp) | 2 | 3 | 5 | 10 |
230 V (kW) | 0.75 | 1.5 | 2.2 | 3 |
400 V (kW) | 1.5 | 3 | 4 | 5.5 |
Overload cycle according to EN 60947-4-2 |
4A: AC53a; 3-5; 75-10 | 7A: AC53a; 3-5; 75-10 | 9A: AC53a; 3-5; 75-10 | 12A: AC53a; 3-5; 75-10 |
Wire Specifications | ||||
Power terminals Single conductor—solid or stranded (AWG) |
18–10 | 18–10 | 18–10 | 18–10 |
Terminal torque (lb-in) |
11 | 11 | 11 | 11 |
Control signals Single conductor—solid or stranded (AWG) |
18–10 | 18–10 | 18–10 | 18–10 |
Terminal torque (lb-in) | 11 | 11 | 11 | 11 |
Power Section | ||||
Rated impulse withstand voltage (Uimp 1.2/ 50 s) |
4 kV | 4 kV | 4 kV | 4 kV |
Rated insulation voltage | 500 | 500 | 500 | 500 |
Control Commands—Vac/Vdc | ||||
Supply voltage control board Us nominal (Vac/Vdc) |
20.4–26.4 | 20.4–26.4 | 20.4–26.4 | 20.4–26.4 |
Current consumption at 24 Vac/Vdc (mA) | 1.6 | 1.6 | 1.6 | 1.6 |
Pick-up voltage | +17.3–+27 | +17.3–+27 | +17.3–+27 | +17.3–+27 |
Drop-out voltage | +3–0 | +3–0 | +3–0 | +3–0 |
Relay Outputs | ||||
Number of relays | 1 (TOR) | 1 (TOR) | 1 (TOR) | 1 (TOR) |
Maximum voltage (Vac) | 250 | 250 | 250 | 250 |
Maximum current (A) | 1A | 1A | 1A | 1A |
Soft Start Functions | ||||
Start ramp (s) | 1–30 | 1–30 | 1–30 | 1–30 |
Stop ramp (s) | 0–30 | 0–30 | 0–30 | 0–30 |
Initial voltage % line voltage DS7-342… |
30–92% | 30–92% | 30–92% | 30–92% |
Initial voltage % line voltage DS7-340… |
30–100% | 30–100% | 30–100% | 30–100% |
Initial voltage % line voltage DS7-34D… |
30–92% | 30–92% | 30–92% | 30–92% |
Control Commands—Vac | ||||
Supply voltage control board Us nominal (Vac) |
102–253 | 102–253 | 102–253 | 102–253 |
Current consumption at 24 Vac/Vdc (mA) | 4 | 4 | 4 | 4 |
Pick-up voltage (Vac) | 102–230 | 102–230 | 102–230 | 102–230 |
Drop-out voltage (Vac) | 0–28 | 0–28 | 0–28 | 0–28 |
Relay Outputs | ||||
Number of relays | 1 (TOR) | 1 (TOR) | 1 (TOR) | 1 (TOR) |
Maximum voltage (Vac) | 250 | 250 | 250 | 250 |
Maximum current (A) | 3A | 3A | 3A | 3A |
Soft Start Functions | ||||
Start ramp (s) | 1–30 | 1–30 | 1–30 | 1–30 |
Stop ramp (s) | 0–30 | 0–30 | 0–30 | 0–30 |
Initial voltage % line voltage | 30–92% | 30–92% | 30–92% | 30–92% |
DS7-342SX004N0-N Dimensions |
---|
DS7 Part Number Selection Guide |
---|