hp & kW Ratings - 10 Second Ramp, One Start per Hour,
|
Motor Power (hp) |
Motor Power (kW) |
Maximum Allowable Breaker Size |
Maximum Allowable Fuse Size |
|||||
---|---|---|---|---|---|---|---|---|
Rated Current (A) |
200 V | 230 V | 480 V | Rated Current (A) |
230 V | 400 V | ||
32 | 7.5 | 10 | 20 | 32 | 7.5 | 15 | HFD3070 | 50A Class RK5 |
Motor Power (hp) |
Motor Power (kW) |
Maximum Allowable Breaker Size |
Maximum Allowable Fuse Size |
|||||
---|---|---|---|---|---|---|---|---|
Rated Current (A) |
200 V | 230 V | 480 V | Rated Current (A) |
230 V | 400 V | ||
22 | 5 | 7.5 | 15 | 24 | 5.5 | 11 | HFD3070 | 50A Class RK5 |
XTOB Overload (Direct Connect) (1) |
XTOE Overload (1) |
PKE MMP | MMP (1) | Connection Kit to MMP |
---|---|---|---|---|
XTOB032CC1 | XTOE045CCS | XTPE032BCS | XTPR032BC1 | XTPAXTPCC |
DS7-340SX032N0-N Specifications |
---|
Rated Control Circuit | Part Number | ||
---|---|---|---|
24 Vac/Vdc 110/230 Vac 24 Vdc |
DS7-340SX016N0-N DS7-342SX016N0-N DS7-34DSX016N0-D |
DS7-340SX024N0-N DS7-342SX024N0-N DS7-34DSX024N0-D |
DS7-340SX032N0-N DS7-342SX032N0-N DS7-34DSX032N0-D |
General | |||
Standards | IEC/EN 60947-4-2; GB14048.6; UL508; CSA-C22.2 No 0-M91; CSA-C22.2 No 14-05 CE marking |
IEC/EN 60947-4-2; GB14048.6; UL508; CSA-C22.2 No 0-M91; CSA-C22.2 No 14-05 CE marking |
IEC/EN 60947-4-2; GB14048.6; UL508; CSA-C22.2 No 0-M91; CSA-C22.2 No 14-05 CE marking |
Certifications marking |
UL/CE/CSA/C-Tick | UL/CE/CSA/C-Tick | UL/CE/CSA/C-Tick |
Ambient temperature (operation) °C |
0 to 40 °C, above 40 °C de-rate linearly by 1% of rated current per Celsius to 60 °C –40 to +40 °C for low temperature version |
0 to 40 °C, above 40 °C de-rate linearly by 1% of rated current per Celsius to 60 °C –40 to +40 °C for low temperature version |
0 to 40 °C, above 40 °C de-rate linearly by 1% of rated current per Celsius to 60 °C –40 to +40 °C for low temperature version |
Ambient temperature (storage) °C | –25 to 55 °C | –25 to 55 °C | –25 to 55 °C |
Altitude | 0–1000m, above 1000m de-rate linearly by 2.5% of rated current per 100m to a maximum of 2000m |
0–1000m, above 1000m de-rate linearly by 2.5% of rated current per 100m to a maximum of 2000m |
0–1000m, above 1000m de-rate linearly by 2.5% of rated current per 100m to a maximum of 2000m |
Installation | Vertical | Vertical | Vertical |
Protection class | IP20 | IP20 | IP20 |
Protection class applies to the front and operator control and display elements. Protection type from all sides is IP00. |
With optional covers from the NZM range, protection type IP40 from all sides can be achieved |
With optional covers from the NZM range, protection type IP40 from all sides can be achieved |
With optional covers from the NZM range, protection type IP40 from all sides can be achieved |
Busbar tag shroud | Back of hand and finger-proof (from front face) |
Back of hand and finger-proof (from front face) |
Back of hand and finger-proof (from front face) |
Overvoltage category/ pollution degree |
II/2 | II/2 | II/2 |
Shock resistance | 8g/11ms | 8g/11ms | 8g/11ms |
Vibration resistance according to EN 60721-3-2 |
2M2 | 2M2 | 2M2 |
Mean heat dissipation at rated duty cycle (W) |
0.8 | 1.1 | 1.5 |
Radio interference | B | B | B |
Main Circuit | |||
Rated operational voltage (V) |
230–460 Vac | 230–460 Vac | 230–460 Vac |
Mains frequency (Hz) | 50/60 Hz | 50/60 Hz | 50/60 Hz |
Rated operation current AC 53 (Ie) |
16 | 24 | 32 |
Motor Power Ratings | |||
200 V (hp) | 3 | 5 | 10 |
230 V (hp) | 5 | 7.5 | 10 |
480 V (hp) | 10 | 15 | 25 |
230 V (kW) | 4 | 5.5 | 7.5 |
400 V (kW) | 7.5 | 11 | 15 |
Overload cycle according to EN 60947-4-2 |
16A: AC53a; 3-5; 75-10 | 24A: AC53a; 3-5; 75-10 | 32A: AC53a; 3-5; 75-10 |
Wire Specifications | |||
Power terminals Single conductor—solid or stranded (AWG) |
18-6 | 18-6 | 18-6 |
Terminal torque (lb-in) |
11 | 11 | 11 |
Control signals Single conductor—solid or stranded (AWG) |
18–10 | 18–10 | 18–10 |
Terminal torque (lb-in) | 11 | 11 | 11 |
Power Section | |||
Rated impulse withstand voltage (Uimp 1.2/ 50 s) |
4 kV | 4 kV | 4 kV |
Rated insulation voltage | 500 | 500 | 500 |
Control Commands—Vac/Vdc | |||
Supply voltage control board Us nominal (Vac/Vdc) |
20.4–26.4 | 20.4–26.4 | 20.4–26.4 |
Current consumption at 24 Vac/Vdc (mA) | 1.6 | 1.6 | 1.6 |
Pick-up voltage | +17.3–+27 | +17.3–+27 | +17.3–+27 |
Drop-out voltage | +3–0 | +3–0 | +3–0 |
Relay Outputs | |||
Number of relays | 2 (TOR, Ready) | 2 (TOR, Ready) | 2 (TOR, Ready) |
Maximum voltage (Vac) | 250 | 250 | 250 |
Maximum current (A) | 1A | 1A | 1A |
Soft Start Functions | |||
Start ramp (s) | 1–30 | 1–30 | 1–30 |
Stop ramp (s) | 0–30 | 0–30 | 0–30 |
Initial voltage % line voltage DS7-342… |
30–92% | 30–92% | 30–92% |
Initial voltage % line voltage DS7-340… |
30–100% | 30–100% | 30–100% |
Initial voltage % line voltage DS7-34D… |
30–92% | 30–92% | 30–92% |
Control Commands—Vac | |||
Supply voltage control board Us nominal (Vac) |
102–253 | 102–253 | 102–253 |
Current consumption at 24 Vac/Vdc (mA) | 4 | 4 | 4 |
Pick-up voltage (Vac) | 102–230 | 102–230 | 102–230 |
Drop-out voltage (Vac) | 0–28 | 0–28 | 0–28 |
Relay Outputs | |||
Number of relays | 2 (TOR, Run) | 2 (TOR, Run) | 2 (TOR, Run) |
Maximum voltage (Vac) | 250 | 250 | 250 |
Maximum current (A) | 3A | 3A | 3A |
Soft Start Functions | |||
Start ramp (s) | 1–30 | 1–30 | 1–30 |
Stop ramp (s) | 0–30 | 0–30 | 0–30 |
Initial voltage % line voltage | 30–92% | 30–92% | 30–92% |
DS7-340SX032N0-N Dimensions |
---|
DS7 Part Number Selection Guide |
---|
© 2016 KMParts.com, Inc. All rights reserved.