Eaton
LGSDC3250FAG
Direct Current
Molded Case Circuit Breaker



Direct Current
Circuit Breaker

Part Index
CLICK HERE

LGED (3-Pole) Shown

LGSDC3250FAG
Direct Current Circuit Breaker

Continuous
Amperes
Interruption
Rating
Poles Terminals
250 50 kA @ 600Vdc 3 Line/Load

Wiring Diagrams
Series Connection Diagrams for DC Application

250 Vdc Maximum—Two Poles in Series

Suitable for use on ungrounded systems, or grounded systems that have one end of load (A) connected to grounded terminal, opposite poles in series connection.


Suitable for use on ungrounded systems only.

500 Vdc or 600 Vdc Maximum—Three Poles in Series

Suitable for use on ungrounded systems, or grounded systems that have one end of load (A) connected to grounded terminal, opposite poles in series connection.


Suitable for use on ungrounded systems only.

750 Vdc Maximum—Four Poles in Series

Suitable for use on ungrounded systems, or grounded systems that have one end of load (A) connected to grounded terminal, opposite poles in series connection.


Suitable for use on ungrounded systems only.

Quick Reference
Direct Current Circuit Breakers

UL 489 Interrupting Capacity Ratings
Circuit
Breaker
Type
Maximum
Amperes
Interrupting Capacity (kA) - Volts DC(1)
125 Poles
in
Series
250(1) Poles
in
Series
500 600 Poles
in
Series
750(2) Poles
in
Series
EGEDC 100 10 1 35 2 35 3
EGSDC 100 35 1 42 2 50 3
EGHDC 100 42 1 50 2 65 3
HFDDC 225 42 1 50 2 42 3 42 4
JGEDC 250 35 1 35 2 35 3
JGSDC 250 42 1 42 2 50 3
JGHDC 250 50 1 50 2 65 3
HJDDC 250 42 1 50 2 42 3
HKDDC 400 42 1 50 2 42 3
LGEDC 600 22 1 22 2 35 3
LGSDC 600 22 1 22 2 50 3
LGHDC 600 50 1 50 2 65 3
HLDDC 600 42 1 50 2 35 3
HLDDC(2) 1200 42 1 50 2
HMDLDC 800 42 1 50 2 35 3
NBDC 1200 42 1 50 2 50 3
RGHDC 3000 42 1 50 2 65 3
IEC 60947-2 Interrupting Capacity Ratings
Circuit Breaker
Type
Maximum
Amperes
125 Volts DC 250 Volts DC 600 Volts DC
Icu Ics Poles in
Series
Icu Ics Poles in
Series
Icu Ics Poles in
Series
EGEDC 100 10 10 1 10 10 2
EGSDC 100 35 35 1 35 35 2
EGHDC 100 42 42 1 42 42 2
JGEDC 250 22 22 1 22 22 2
JGSDC 250 22 22 1 22 22 2
JGHDC 250 42 42 1 42 42 2
HJDDC 250 20 10 3
LGEDC 600 22 22 1 22 22 2
LGSDC 600 22 22 1 22 22 2
LGHDC 600 42 42 1 42 42 2
HLDDC 600 20 10 3
HMDLDC 800 20 10 3

NOTES:
(1) DC ratings apply to substantially non-inductive circuits. Time constants per UL 489.
(2) EGEDC through HMDLDC have been tested up to 300 Vdc to allow for battery charging voltages. 750 Vdc is common in transportation applications. HFDDC, four-pole 750 Vdc is available up to 150A maximum. 300 Vdc and 750 Vdc are not UL 489 listed voltage ratings.
(3) Four-pole frame with two-poles connected in parallel.

Dimensions

Frame Number
of Poles
Width Height Depth
EGEDC, EGSDC, EGHDC 3 3.00 (76.2) 5.50 (139.7) 2.99 (75.9)
HFDDC 1 1.38 (35.1) 6.00 (152.4) 3.38 (86.0)
2 2.75 (70.0) 6.00 (152.4) 3.38 (86.0)
3 4.13 (105.0) 6.00 (152.4) 3.38 (86.0)
4  5.50 (139.7) 6.00 (152.4) 3.38 (86.0)
JGEDC, JGSDC, JGHDC 3 4.13 (104.9) 7.00 (177.8) 3.57 (90.7)
HJDDC 2, 3 4.13 (105.0) 10.00 (254.0) 4.06 (103.1)
HKDDC 2, 3 5.50 (139.7 10.13 (257.3) 4.10 (104.1)
LGEDC, LGSDC, LGHDC 3 5.48 (139.2) 10.13 (257.3) 4.09 (103.9)
600A Max. HLDDC 2, 3 8.25 (209.6) 10.75 (273.1) 4.06 (103.1)
1200A Max. HLDDC 4 11.00 (279.4) 10.75 (273.1) 4.06 (103.1)
HMDLDC 2, 3 8.25 (209.6) 16.00 (406.4) 4.06 (103.1)
NBDC 3 8.25 (209.6) 16.00 (406.4) 5.50 (139.7)
RGHDC 3 15.50 (393.7) 16.00 (406.4) 9.75 (247.7)