MCPs for Application with Motor Starters Equipped with Electronic Overload Relays 600 Vac Maximum, 250 Vdc Maximum |
||||
NEMA Starter Size |
Continuous Amps |
Cam Setting |
Motor Full Load Current Amperes (FLA)(1) |
MCP Trip Setting(2) |
---|---|---|---|---|
4 | 150 | A | 57.0–75.0 | 750 |
B | 76.0–95.0 | 1000 | ||
C | 96.0–114.0 | 1250 | ||
D | 115.0–130.7 | 1500 | ||
E | (3) | 1750 | ||
F | (3) | 2000 | ||
G | (3) | 2250 | ||
H | (3) | 2500 |
NOTES:
(1) Motor FLA ranges are typical. The corresponding trip setting is at 13 x the minimum FLA value shown. Where a 13 x setting is required for an intermediate FLA value, alternate Cam settings and/or MCP ratings should be used.
(2) For DC applications, actual trip levels are approximately 40% higher than values shown.
(3) Settings above 130A are for special applications. NEC Article 430.110(a) requires the ampere rating of the disconnecting means to be not less than 115% of the motor full load ampere rating. HMCP 25–100A come with line and load steel body terminals, 3T100FB.