HMCPS150U4C
Motor Circuit Protection (MCP)
for Application with Motor Starters
Equipped with Electronic Overload Relays


Eaton HMCPS150U4C Motor Circuit Protection (MCP) for Application with Motor Starters Equipped with Electronic Overload Relays
Series-C
MCP
Part Index
CLICK HERE

HMCP (3-Pole) Shown

HMCPS150U4C Motor Circuit Protection (MCP)

MCPs for Application with Motor Starters Equipped
with Electronic Overload Relays
600 Vac Maximum, 250 Vdc Maximum
NEMA
Starter
Size
Continuous
Amps
Cam
Setting
Motor
Full Load
Current
Amperes
(FLA)(1)
MCP
Trip
Setting(2)
4 150 A 57.0–75.0 750
B 76.0–95.0 1000
C 96.0–114.0 1250
D 115.0–130.7 1500
E (3) 1750
F (3) 2000
G (3) 2250
H (3) 2500

NOTES:
(1) Motor FLA ranges are typical. The corresponding trip setting is at 13 x the minimum FLA value shown. Where a 13 x setting is required for an intermediate FLA value, alternate Cam settings and/or MCP ratings should be used.

(2) For DC applications, actual trip levels are approximately 40% higher than values shown.

(3) Settings above 130A are for special applications. NEC Article 430.110(a) requires the ampere rating of the disconnecting means to be not less than 115% of the motor full load ampere rating. HMCP 25–100A come with line and load steel body terminals, 3T100FB.