Series-C MCP Part Index CLICK HERE |
|
HMCP (3-Pole) Shown |
MCPs for Application with Motor Starters Equipped with Electronic Overload Relays 600 Vac Maximum, 250 Vdc Maximum |
||||
NEMA Starter Size |
Continuous Amps |
Cam Setting |
Motor Full Load Current Amperes (FLA)(1) |
MCP Trip Setting(2) |
---|---|---|---|---|
4 | 150 | A | 34.6–46.0 | 450 |
B | 46.1–57.5 | 600 | ||
C | 57.6–69.1 | 750 | ||
D | 69.2–80.6 | 900 | ||
E | 80.7–92.2 | 1050 | ||
F | 92.3–103.7 | 1200 | ||
G | 103.8–115.2 | 1350 | ||
H | 115.3–126.7 | 1500 |
NOTES:
(1) Motor FLA ranges are typical. The corresponding trip setting is at 13 x the minimum FLA value shown. Where a 13 x setting is required for an intermediate FLA value, alternate Cam settings and/or MCP ratings should be used.
(2) For DC applications, actual trip levels are approximately 40% higher than values shown.