HMCP (3-Pole) Shown |
MCPs for Application with Motor Starters Equipped with Electronic Overload Relays 600 Vac Maximum, 250 Vdc Maximum |
||||
NEMA Starter Size |
Continuous Amps |
Cam Setting |
Motor Full Load Current Amperes (FLA)(1) |
MCP Trip Setting(2) |
---|---|---|---|---|
1 | 30 | A | 6.9–9.1 | 90 |
B | 9.2–11.4 | 120 | ||
C | 11.5–13.7 | 150 | ||
D | 13.8–16.0 | 180 | ||
E | 16.1–18.3 | 210 | ||
F | 18.4–20.6 | 240 | ||
G | 20.7–22.9 | 270 | ||
H | 23.0–25.2 | 300 |
NOTES:
(1) Motor FLA ranges are typical. The corresponding trip setting is at 13 x the minimum FLA value shown. Where a 13 x setting is required for an intermediate FLA value, alternate Cam settings and/or MCP ratings should be used.
(2) For DC applications, actual trip levels are approximately 40% higher than values shown.