Series-C MCP Part Index CLICK HERE |
|
HMCP (3-Pole) Shown |
MCPs for Application with Motor Starters Equipped with Electronic Overload Relays 600 Vac Maximum, 250 Vdc Maximum |
||||
NEMA Starter Size |
Continuous Amps |
Cam Setting |
Motor Full Load Current Amperes (FLA)(1) |
MCP Trip Setting(2) |
---|---|---|---|---|
0 | 15 | A | 3.4–4.5 | 45 |
B | 4.6–5.6 | 60 | ||
C | 5.7–6.8 | 75 | ||
D | 6.9–7.9 | 90 | ||
E | 8.0–9.1 | 105 | ||
F | 9.2–10.3 | 120 | ||
G | 10.4–11.4 | 135 | ||
H | 11.5–12.6 | 150 |
NOTES:
(1) Motor FLA ranges are typical. The corresponding trip setting is at 13 x the minimum FLA value shown. Where a 13 x setting is required for an intermediate FLA value, alternate Cam settings and/or MCP ratings should be used.
(2) For DC applications, actual trip levels are approximately 40% higher than values shown.