Eaton
|
|
Series-C MCP Part Index CLICK HERE |
|
HMCP (3-Pole) Shown |
MCPs for Application with Motor Starters Equipped with Electronic Overload Relays 600 Vac Maximum, 250 Vdc Maximum |
||||
NEMA Starter Size |
Continuous Amps |
Cam Setting |
Motor Full Load Current Amperes (FLA)(1) |
MCP Trip Setting(2) |
---|---|---|---|---|
0 | 7 | A | 1.5–2.0 | 21 |
B | 2.1–2.5 | 28 | ||
C | 2.6–3.1 | 35 | ||
D | 3.2–3.6 | 42 | ||
E | 3.7–3.9 | 49 | ||
F | 4.3–4.7 | 56 | ||
G | 4.8–5.2 | 63 | ||
H | 5.3–5.7 | 70 |
NOTES:
(1) Motor FLA ranges are typical. The corresponding trip setting is at 13 x the minimum FLA value shown. Where a 13 x setting is required for an intermediate FLA value, alternate Cam settings and/or MCP ratings should be used.
(2) For DC applications, actual trip levels are approximately 40% higher than values shown.