Series-C MCP Part Index CLICK HERE |
|
HMCP (3-Pole) Shown |
MCPs for Application with Motor Starters Equipped with Electronic Overload Relays 600 Vac Maximum, 250 Vdc Maximum |
||||
NEMA Starter Size |
Continuous Amps |
Cam Setting |
Motor Full Load Current Amperes (FLA)(1) |
MCP Trip Setting(2) |
---|---|---|---|---|
0 | 3 | A | 0.69–0.91 | 9 |
B | 0.92–1.0 | 12 | ||
C | 1.1–1.2 | 15 | ||
D | 1.3–1.5 | 18 | ||
E | 1.6–1.7 | 21 | ||
F | 1.8–1.9 | 24 | ||
G | 2.0–2.2 | 27 | ||
H | 2.3–2.5 | 39 |
NOTES:
(1) Motor FLA ranges are typical. The corresponding trip setting is at 13 x the minimum FLA value shown. Where a 13 x setting is required for an intermediate FLA value, alternate Cam settings and/or MCP ratings should be used.
(2) For DC applications, actual trip levels are approximately 40% higher than values shown.