Series-C MCP Part Index CLICK HERE |
|
HMCP (3-Pole) Shown |
F-Frame — 600 Vac Maximum, 250 Vdc Maximum | ||||
NEMA Starter Size |
Continuous Amps |
Cam Setting |
Motor Full Load Current Amperes (FLA)(1) |
MCP Trip Setting(2) |
---|---|---|---|---|
4 | 150 | A | 57.0 –75.0 | 750 |
B | 76.0–95.0 | 1000 | ||
C | 96.0–114.0 | 1250 | ||
D | 115.0–130.7 | 1500 | ||
E | (2) | 1750 | ||
F | (2) | 2000 | ||
G | (2) | 2250 | ||
H | (2) | 2500 |
NOTES:
(1) Motor FLA ranges are typical. The corresponding trip setting is at 13 x the minimum FLA value shown. Where a 13 x setting is required for an intermediate FLA value, alternate Cam settings and/or MCP ratings should be used.
(2) Settings above 130 amperes are for special applications. NEC Article 430.110(a) requires the ampere rating of the disconnecting means to be not less than 115% of the motor full load ampere rating.
All GMCP 3–63A come with line and load steel body terminals for Cu only wire.
UL recognized and CSA approved