Special Low Magnetic Protection Application MCP — 600 Vac Maximum, 250 Vdc Maximum |
||
Continuous Amps |
Cam Setting |
MCP Trip Setting(1) |
---|---|---|
100 | A | 160 |
B | 174 | |
C | 185 | |
D | 196 | |
E | 207 | |
F | 218 | |
G | 229 | |
H | 240 |
NOTES:
(1) For DC applications, actual trip levels are approximately 40% higher than values shown.
HMCP 25–100A come with line and load steel body terminals, 3T100FB.