Eaton
|
|
Series-C MCP Part Index CLICK HERE |
|
HMCP (3-Pole) Shown |
F-Frame — 600 Vac Maximum, 250 Vdc Maximum | ||||
NEMA Starter Size |
Continuous Amps |
Cam Setting |
Motor Full Load Current Amperes (FLA)(1) |
MCP Trip Setting(2) |
---|---|---|---|---|
2 | 50 | A | 11.5–15.2 | 150 |
B | 15.3–19.1 | 200 | ||
C | 19.2–22.9 | 250 | ||
D | 23.0–26.8 | 300 | ||
E | 26.9–30.6 | 350 | ||
F | 30.7–4.5 | 400 | ||
G | 34.6–38.3 | 450 | ||
H | 38.4–42.1 | 500 |
NOTES:
(1) Motor FLA ranges are typical. The corresponding trip setting is at 13 x the minimum FLA value shown. Where a 13 x setting is required for an intermediate FLA value, alternate Cam settings and/or MCP ratings should be used.
(2) For DC applications, actual trip levels are approximately 40% higher than values shown.
All GMCP 3–63A come with line and load steel body terminals for Cu only wire.
UL recognized and CSA approved
© 2015 KMParts.com, Inc. All rights reserved.