Eaton
|
|
Series-C MCP Part Index CLICK HERE |
|
HMCP (3-Pole) Shown |
Special Low Magnetic Protection Application MCP — 600 Vac Maximum, 250 Vdc Maximum |
||
Continuous Amps |
Cam Setting |
MCP Trip Setting(1) |
---|---|---|
25 | A | 40 |
B | 43 | |
D | 49 | |
E | 52 | |
F | 55 | |
G | 58 | |
H | 60 |
NOTES:
(1) For DC applications, actual trip levels are approximately 40% higher than values shown.
HMCP 25–100A come with line and load steel body terminals, 3T100FB.
© 2015 KMParts.com, Inc. All rights reserved.