HMCP015E0C
Motor Circuit Protection (MCP)


Eaton HMCP015E0C Motor Circuit Protection (MCP)
Series-C
MCP
Part Index
CLICK HERE

HMCP (3-Pole) Shown

HMCP015E0C Motor Circuit Protection (MCP)

F-Frame — 600 Vac Maximum, 250 Vdc Maximum
NEMA
Starter
Size
Continuous
Amps
Cam
Setting
Motor
Full Load
Current
Amperes
(FLA)(1)
MCP
Trip
Setting(2)
0 15 A 3.4–4.5 45
B 4.6–5.6 60
C 5.7–6.8 75
D 6.9–7.9 90
E 8.0–9.1 105
F 9.2–10.3 120
G 10.4–11.4 135
H 11.5 –12.6 150

NOTES:
(1) Motor FLA ranges are typical. The corresponding trip setting is at 13 x the minimum FLA value shown. Where a 13 x setting is required for an intermediate FLA value, alternate Cam settings and/or MCP ratings should be used.

(2) For DC applications, actual trip levels are approximately 40% higher than values shown.

All GMCP 3–63A come with line and load steel body terminals for Cu only wire.

UL recognized and CSA approved




Let our expert sales staff guide you through finding the right products to fit your needs. CALL 866-595-9616.