Eaton
|
|
Series-C MCP Part Index CLICK HERE |
|
GMCP (3-Pole) Shown |
F-Frame — 600 Vac Maximum, 250 Vdc Maximum | ||||
NEMA Starter Size |
Continuous Amps |
Cam Setting |
Motor Full Load Current Amperes (FLA)(1) |
MCP Trip Setting(2) |
---|---|---|---|---|
3 | 60 | A | 23.1–27.5 | 300 |
B | 27.7–32.2 | 360 | ||
C | 32.3–36.7 | 420 | ||
D | 36.9–41.4 | 480 | ||
E | 41.5–46.0 | 540 | ||
F | 46.2–50.5 | 600 |
NOTES:
(1) Motor FLA ranges are typical. The corresponding trip setting is at 13 x the minimum FLA value shown. Where a 13 x setting is required for an intermediate FLA value, alternate Cam settings and/or MCP ratings should be used.
All GMCP 3–63A come with line and load steel body terminals for Cu only wire.
UL recognized and CSA approved
© 2015 KMParts.com, Inc. All rights reserved.