Eaton
|
|
Series-C MCP Part Index CLICK HERE |
|
GMCP (3-Pole) Shown |
F-Frame — 600 Vac Maximum, 250 Vdc Maximum | ||||
NEMA Starter Size |
Continuous Amps |
Cam Setting |
Motor Full Load Current Amperes (FLA)(1) |
MCP Trip Setting(2) |
---|---|---|---|---|
0 | 7 | A | 2.6–3.1 | 35 |
B | 3.2–3.6 | 42 | ||
C | 3.7–3.9 | 49 | ||
D | 4.3–4.7 | 56 | ||
E | 4.8–5.2 | 63 | ||
F | 5.3–5.7 | 70 |
NOTES:
(1) Motor FLA ranges are typical. The corresponding trip setting is at 13 x the minimum FLA value shown. Where a 13 x setting is required for an intermediate FLA value, alternate Cam settings and/or MCP ratings should be used.
All GMCP 3–63A come with line and load steel body terminals for Cu only wire.
UL recognized and CSA approved
© 2015 KMParts.com, Inc. All rights reserved.