Eaton
|
|
![]() |
Series-C Frame Size - G Part Index CLICK HERE |
Type GD (2-Pole) Shown |
Number of Poles |
Amperes | Volts | Type of Trip(1) |
Federal Specification W-C-375b |
Terminals | |
---|---|---|---|---|---|---|
AC | DC | |||||
2 | 20 | 480 | 125/250 | Non- Interchangeable (N.I.T.U.) |
13b | Line/Load |
Circuit Breaker Type |
Continuous Ampere Rating at 40°C |
No. of Poles |
UL Listed Interrupting Ratings (rms Symmetrical Amperes) | |||||||
---|---|---|---|---|---|---|---|---|---|---|
AC (kA) | DC (kA)(2) | |||||||||
120 | 120/240 | 240 | 277 | 480 | 600 | 125 | 250 | |||
GHB | 15–100(3) | 1 | 65 | — | — | — | — | — | 14 | — |
GHB | 15–100 | 2, 3 | — | — | 65 | — | — | — | — | 14 |
GHB | 15–100 | 1 | — | — | — | 14 | — | — | 14 | — |
GHB | 15–100 | 2, 3 | — | — | — | 14 | 14 | — | — | 14 |
HGHB | 15–30 | 1 | 65 | — | — | 25 | — | — | 14 | — |
GHQ | 15–20 | 1 | 65 | — | — | 14 | — | — | — | — |
GHBS | 15–30 | 1, 2 | 65 | 65 | — | 14 | — | — | — | — |
GBHS | 15–20 | 1, 2 | — | — | — | — | — | 10 | — | — |
GDB | 15–50 | 2 | — | — | — | — | 14 | — | — | 10 |
GDB | 15–100 | 3 | — | — | — | — | 14 | — | — | 10 |
GD | 15–50 | 2 | — | — | 65 | — | 14 | — | — | 10 |
GD | 15–100 | 3 | — | — | 65 | — | 22 | — | — | 10 |
GHC | 15–100 | 1 | 65 | — | — | — | — | — | 14 | — |
GHC | 15–100 | 2, 3 | — | — | 65 | — | — | — | — | 1 |
GHC | 15–100 | — | — | — | 14 | — | — | 14 | — | |
GHC | 15–100 | 2, 3 | — | — | — | 14 | 14 | — | — | 14 |
HGHC | 15–30 | 1 | 65 | — | — | 25 | — | — | 14 | — |
NOTES:
(1) N.I.T.U. is non-interchangeable trip unit and I.T.U. is interchangeable trip unit.
(2) Two-pole circuit breaker, or two poles of three-pole circuit breaker at 250 Vdc.
(3) Not defined in W-C-375b.
(4) Current limiting.
(5) Check with Eaton for availability.
![]() |