BUY HERE
CALL NOW
IN STOCK
866.595.9616

Eaton
FDPV4100W
PVGard Solar Photovoltaic
Circuit Breaker



PVGard Solar Photovoltaic
Circuit Breaker

Part Index
CLICK HERE

FD-PV (3-Pole) Shown

FDPV4100W
PVGard Solar Photovoltaic Circuit Breaker

Continuous
Amperes
Capacity
(per pole)
Trip Unit Poles Rating
100 3 kA @ 1000Vdc Fixed thermal,
Fixed magnetic
4 80%

Technical Data and Specifications

  JG PVS KD PVS
Number of 600 Vdc circuits 3 3
Maximum voltage rating 600 Vdc 600 Vdc
Ampere range 90–250A 100–400A
Interrupting capacity at 600 Vdc  1.2 kA 3 kA
Time constant 1 ms 1 ms
Trip unit type  Thermal-magnetic Thermal-magnetic

Rated impulse withstand voltage

Main conducting paths
Auxiliary circuits


8 kV
4 kV

8 kV
4 kV

Endurance

Mechanical operations
Electrical operations
Maximum switching frequency

10,000
400
240 per hour

6000
400
240 per hour
Third-party certification  UL 489B UL 489B

Environment

Design ambient temperature
Maximum current at 60°C, as % of rated current
Maximum current at 70°C, as % of rated current

50°C
93%
85%

50°C
93%
85%
Operating temperature range
Storage temperature range
Suitable for freeze temperatures to –40°C
Relative humidity
–20°C to +50°C
–20°C to +70°C
Option
0 to 95% noncondensing
–20°C to +50°C
–20°C to +70°C
Option
0 to 95% noncondensing
Suitable for reverse-feed applications  Yes Yes
Mounting—permissible mounting position
Weight in lbs  6.6 11.42

Wiring Diagrams
Series Connection Diagrams for DC Application

JF PVS, KD PVS—600 Vdc Per-Pole

Suitable for grounded or ungrounded systems. Suitable for quantity (3) 600 Vdc circuits.


FD PV, KD PV, LG PV—1000 Vdc Maximum—Four Poles-in-Series

Suitable for use on ungrounded systems, or grounded systems that have one end of load (A) connected to grounded terminal, opposite poles in series connection.


Suitable for use on ungrounded systems only.

MDL PV—1000 Vdc Maximum—Three Poles in Series

Suitable for use on ungrounded systems, or grounded systems that have one end of load (A) connected to grounded terminal, opposite poles in series connection.


Suitable for use on ungrounded systems only.

Notes:
(1) Poles in series connection is customer supplied. Use rated cable per NEC
(2) For grounded systems, all poles in series must be connected on non-grounded terminal, with load connected to grounded terminal.

Dimensions

PVGard Solar Circuit Breakers—600 Vdc Per-Pole
Frame Number of
Circuits in
a Frame
Width Height Depth
JG PVS 3 4.13 (104.9) 7.00 (177.8) 3.44 (87.4)
KD PVS 3 5.49 (139.4) 10.13 (257.2) 4.31 (109.6)
PVGard Solar Circuit Breakers—1000 Vdc Poles-in-Series
FD PV 4 5.50 (139.7) 6.00 (152.4) 3.38 (86.0)
KD PV 4 7.22 (183.4) 10.13 (257.3) 4.09 (103.9)
KD PV 4 7.22 (183.4) 10.13 (257.3) 4.09 (103.9)
LG PV 4 7.22 (183.4) 10.13 (257.3) 4.09 (103.9)
MDL PV 3 8.25 (209.6) 16.00 (406.4) 4.06 (103.1)



Let our expert sales staff guide you through finding the right products to fit your needs. CALL 866-595-9616.