Menu


Moeller PKZM0-xx/S00
Magnetic Motor Protector Combination Index

The S00 contactor is identical to to the SE00,
except for the built-in current limiting contact assembly,
which makes it suitable for "Type 2" coordination levels
per IEC/EN 60 947 and no welding performance in combination
with the PKZM0 motor protector.

pkzm0se00 Hp @ 230 Hp @ 460 Amps Amps Amps Amps Amps
PKZM0-xx/SE00
Moeller Electric PKZM0-xx/SE00
 
UL/CSA 3-phase HP ratings

 UL/CSA Short circuit current rating @ 600 V AC

kA

Max. listed branch circuit protective fuse

A

Max. listed branch circuit protective breaker

A

Adjustable Thermal Range

 

A

Response current of magnetic trips

A

 
PKZM0-0.16/SE00 In this range, select motor protector in accordance with the motor nameplate full load current

 

50 600 600 0.1 - 0.16 2.2

PKZM0-0.25/SE00

50 600 600 0.16 - 0.25 3.5

PKZM0-0.4/SE00

50 600 600 0.25 - 0.4 5.6

PKZM0-0.63/SE00

50 600 600 0.4 - 0.63 8.8

PKZM0-1/SE00

  1/2 50 600 600 0.63 - 1 14

PKZM0-1.6/SE00

3/4 50 600 600 1 - 1.6 22

PKZM0-2.5/SE00

1/2 1 50 600 600 1.6 - 2.5 35

PKZM0-4/SE00

1 2 50 600 600 2.5 - 4 56

PKZM0-6.3/SE00

1 1/2 3 50 600 600 4 - 6.3 88

PKZM0-10/SE00

3 7 1/2 22 150 125 6.3 - 11 140

Let our expert sales staff guide you through finding the right products to fit your needs. CALL 866-595-9616.