Moeller NZM4
|
600 - 1200 Amps |
Size 4 (N) NORMAL Switching Capacity NZMN4 |
|
240VAC 60Hz | 480VAC 60Hz | |
85 kA | 42 kA |
600 - 1200 Amps | Size 4 (H) HIGH Switching Capacity NZMH4 |
|
240VAC 60Hz | 480VAC 60Hz | |
125 kA | 85 kA |
600 - 1200 Amps |
Size 4 (L) LIMITING Switching Capacity NZML4 |
|
240VAC 60Hz | 480VAC 60Hz | |
kA | kA | |
xxx=Rated Amps - NA=North America NZM(1)(2)(3)(4)-(B)(N)(H)(L)-(A)(AE)(AF)(AEF)(VE)(VEF)(S)(SE)-AMPS-NA |
NZM1
15-125 AMP |
-B
(Basic) |
-A | ( Thermal Magnetic, Adjustable ) | |||
-AE | ( Solid State, Adjustable ) | |||||
NZM2
15-250 AMP |
-N
(Normal) |
-AF | ( Thermal Magnetic, Fixed ) | |||
-AEF | ( Solid State, Fixed ) | |||||
NZM3
125-600 AMP |
-H
(High) |
-M | ( Thermomagnetic release ) | |||
-ME | (Electronic Release ) | |||||
-VE | ( Time Delay, Solid State, Adjustable) | |||||
-VEF | ( Time Delay, Solid State, Fixed ) | |||||
NZM4
300-1200 AMP |
-L
(Limiter) |
-S | ( Instantaneous Only ) | |||
-SE | ( Instantaneous, Solid State ) |
|
Dimensions |
|||
WIDTH | HEIGHT | DEPTH |
NZM1 | 90mm | 145mm | 68mm ( 84.5mm ) |
3.5" | 5.75" | 2.75" ( 3.33") |
NZM2 | 105mm | 206mm | 103mm ( 149mm ) |
4.13" | 8.11" | 4.00" ( 5.87" ) |
NZM3 | 140mm | 300mm | 121mm ( 166mm ) |
5.50" | 11.81" | 4.76" ( 6.54") |
NZM4 | 204 | 401 | 138mm ( 207mm ) |
8.03" | 15.80" | 5.43" ( 8.15" ) |