Eaton
|
|
Series-C MCP Part Index CLICK HERE |
|
HMCP (3-Pole) Shown |
MCPs for Application with Motor Starters Equipped with Electronic Overload Relays 600 Vac Maximum, 250 Vdc Maximum |
||||
NEMA Starter Size |
Continuous Amps |
Cam Setting |
Motor Full Load Current Amperes (FLA)(1) |
MCP Trip Setting(2) |
---|---|---|---|---|
3 | 100 | A | 23.0–30.6 | 300 |
B | 30.7–38.3 | 400 | ||
C | 38.4–46.0 | 500 | ||
D | 46.1–53.7 | 600 | ||
E | 53.8 –61.4 | 700 | ||
F | 61.5 –69.1 | 800 | ||
G | 69.2–76.8 | 900 | ||
H | 76.9–84.5 | 1000 |
NOTES:
(1) Motor FLA ranges are typical. The corresponding trip setting is at 13 x the minimum FLA value shown. Where a 13 x setting is required for an intermediate FLA value, alternate Cam settings and/or MCP ratings should be used.
(2) For DC applications, actual trip levels are approximately 40% higher than values shown.