F-Frame — 600 Vac Maximum, 250 Vdc Maximum | ||||
NEMA Starter Size |
Continuous Amps |
Cam Setting |
Motor Full Load Current Amperes (FLA)(1) |
MCP Trip Setting(2) |
---|---|---|---|---|
2 | 70 | A | 16.1–21.4 | 210 |
B | 21.5 –26.8 | 280 | ||
C | 26.9 –32.2 | 350 | ||
D | 32.3–37.5 | 420 | ||
E | 37.6–42.9 | 490 | ||
F | 43.0–48.3 | 560 | ||
G | 48.4–53.7 | 630 | ||
H | 53.8–59.1 | 700 |
NOTES:
(1) Motor FLA ranges are typical. The corresponding trip setting is at 13 x the minimum FLA value shown. Where a 13 x setting is required for an intermediate FLA value, alternate Cam settings and/or MCP ratings should be used.
(2) For DC applications, actual trip levels are approximately 40% higher than values shown.
All GMCP 3–63A come with line and load steel body terminals for Cu only wire.