Eaton
|
|
Series-C Frame Size - M Part Index CLICK HERE |
|
Type MT Shown |
Number of Poles |
Amperes | For Use With |
Type of Trip |
Terminals |
---|---|---|---|---|
2 | 600 | Standard, High or Ultra-High Interrupting Frames |
Thermal-Magnetic | Standard |
UL 489/CSA Interrupting Capacity Ratings(1) | |||||
Circuit Breaker Type |
Number of Poles |
Interrupting Capacity (kA Symmetrical Amperes) | |||
---|---|---|---|---|---|
Volts AC (50/60 Hz) | Volts DC(2)(3) | ||||
240 | 480 | 600 | 250 | ||
MDL, MDLB | 2, 3 | 65 | 50 | 25 | 22 |
CMDL | 2, 3 | 65 | 50 | 25 | — |
HMDL, HMDLB | 2, 3 | 100 | 65 | 35 | 25 |
CHMDL | 2, 3 | 100 | 65 | 35 | — |
IEC 947-2 Interrupting Capacity Ratings 1 | |||||
Circuit Breaker Type |
Number of Poles |
Interrupting Capacity rms (kA Symmetrical Amperes) ICU ≠ ICS | |||
---|---|---|---|---|---|
Volts AC (50/60 Hz) | Volts DC(2)(3) | ||||
240 | 415 | 690 | 250 | ||
MDL, MDLB | 2, 3 | 65/65 | 50/50 | 20/10 | 20/10 |
CMDL | 2, 3 | 65/65 | 50/50 | 20/10 | — |
HMDL, HMDLB | 2, 3 | 100/100 | 70/50 | 25/13 | 20/10 |
CHMDL | 2, 3 | 100/100 | 70/50 | 25/13 | — |
NOTES:
(1) Utilization Category A circuit breakers.
(2) Two-pole or two poles of three-pole circuit breaker. Thermal-magnetic trip units only, MDL, HMDL breakers with electronic trip unit are not DC rated.
(3) Time constant is 3 milliseconds minimum at 10 kA and 8 milliseconds at 22 kA.
Trip Unit Type | Digitrip RMS 310 | |
rms sensing | Yes | Yes |
Breaker Type | ||
Frame | MDL, MDLB, CMDL, HMDL, HMDLB, CHMDL | MDL, MDLB, CMDL, HMDL, HMDLB, CHMDL |
Ampere range | 400–800A | 400–800A |
Interrupting rating at 480 volts |
50, 65 (kA) | 50, 65 (kA) |
Protection | ||
Ordering options | LS, LSG | LSI, LSIG |
Fixed rated plug (In) |
Yes | Yes |
Overtemperature trip | Yes | Yes |
Long Delay Protection (L) | ||
Adjustable rating plug (In) |
Yes | Yes |
Long delay pickup | 0.5–1.0 (In)(1) | 0.5–1.0 (In)(1) |
Long delay time I2t | 12 seconds | 12 seconds |
Long delay time I4t | No | No |
Long delay thermal memory |
Yes | Yes |
High load alarm | No | No |
Short Delay Protection (S) | ||
Short delay pickup | 200–800% x (In) | 200–800% x (In) |
Short delay time I2t | 100 ms | No |
Short delay time flat | No | Inst–300 ms |
Short delay time zone selective interlocking |
No | No |
Instantaneous Protection (I) | ||
Instantaneous pickup | No | 200–800% x (In) |
Discriminator | No | No |
Instantaneous override | Yes | Yes |
Ground Fault Protection (G) | ||
Ground fault alarm | No | No |
Ground fault pickup | 1–5 x Ig (160A) | 1–5 x Ig (160A) |
Ground fault delay I2t | No | No |
Ground fault delay flat | Inst–500 ms | Inst–500 ms |
Ground fault zone selective interlocking |
No | No |
Ground fault thermal memory |
Yes | Yes |
System Diagnostics | ||
Status LEDs | Yes | Yes |
Cause of trip LEDs | No | No |
Magnitude of trip information | No | No |
Remote signal contacts—ground alarm |
Yes(2) | Yes(2) |
System Monitoring | ||
Digital display | No | No |
Current | No | No |
Power and energy | No | No |
Power quality— harmonics |
No | No |
Power factor | No | No |
Communications | ||
Eaton’s PowerNet | No | No |
Testing | ||
Testing method | Test set | Test set |
Legend In = Rating Plug |
Notes (1) Adjust by rating plug. (2) With separate ground fault alarm unit (GFAU). |
Number of Poles | Width | Height | Depth |
---|---|---|---|
2, 3 | 8.25 (209.6) | 16.00 (406.4) | 4.06 (103.1) |
© 2015 KMParts.com, Inc. All rights reserved.