Menu

PKE12-XTU-12

PKE12-XTU-12

PKE12/XTU-4 shown


PKE12-XTU-12
Motor-Protective Circuit Breakers Standard Complete Devices

Description Setting Range
Overload Release
Old Moeller
Part Number
New Eaton
Part Number
Motor-protective circuit-breaker PKE,
Coordination type "1" and "2"
3.0...12.0A PKE12-XTU-12 XTPE012BCSNL


PKE12-XTU-12 Technical Data

General
Standards and regulations IEC/EN 60947-4-1, VDE0660
UL 508, CSA C22.2 No.14
Climatic proofing Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature Storage -25…80°C
Open -25…55°C
Enclosed -25…40°C
Direction of incoming supply any
Degree of protection Device IP20
Terminals IP00
Touch protection to EN50274 Finger- and back-of-hand-proof
Mechanical shock resistance halfsinusoidal
shock 10 ms to IEC 60068-2-27
25g
Altitude max. 2000m
Screw terminal
conductor cross-section
Solid 1 x (1 – 6) mm(2)
1 x (1 – 6) mm(2)
Stranded with ferrule to
DIN 46228
1 x (1 – 6) mm(2)
1 x (1 – 6) mm(2)
Solid or stranded 18 – 10 AWG
Main conductor 1.7 Nm
Auxiliary conductor 1 Nm
Main circuit
Rated impulse withstand voltage Uimp 6000 V AC
Overvoltage category / pollution degree III/3
Rated operational voltage Ue 690V
Rated uninterrupted current = rated
output current
Iu = Ie 32A or setting value
of the overcurrent release
Rated frequency 40 – 60 Hz
Current heating losses
(3-pole at operating temperature)
6W
Lifespan, mechanical Operations 0.05 x 106
Lifespan, electrical (AC-3 at 400 V) Operations 0.05 x 106
Maximum operating frequency Operations/h 60 ops./h
Motor switching capacity AC AC-3 up to 690 V 32A
Trip release
Temperature compensation
-25…55 °C
-25…55 °C
Temperature compensation residual
error for T > 40°C
Overload release setting range  0.25 – 1
Short-circuit release tolerance + 20%
Single-phasing sensitivity IEC/EN 60947-4-1, VDE 0660 part 102


PKE12-XTU-12 Dimensions

Inches  
Millimeters
 
=  

Let our expert sales staff guide you through finding the right products to fit your needs. CALL 866-595-9616.